Object 0x605D: Halt option code
This parameter determines which action should be taken if bit 8 (halt) in the controlword
is active.
Object description:
Index 605Dh
Name Halt option code
Object code VAR
Data type INTEGER16
Category Optional
Entry description:
Access Read/write
PDO mapping No
Value range INTEGER16
Default value 1
Data description:
Value Description
-32,768…-1 Manufacturer specific
0 Disable drive function
1 Slow down on slow-down ramp
2 Slow down on quick-stop ramp
3 Slow down on current limit (only for tq mode)
3…32,767 Reserved
In Profile Position mode, the Halt option is not affected when this object is set.